Annunciator Digital Output Function Selection
From EMIT Controls
Revision as of 13:33, 2 November 2023 by Thomas Peterson (talk | contribs)
The annunciator digital output selection screen can be used to assign common built-in functions to the digital outputs. This page is shown below.
In some cases, the setup screen for a particular function will already have a box to select an output (For example, see "Idle Hold Setup").
However, for some functions, the only way to assign the output is through this screen. Also, it might be desirable to have two outputs have the same function.
To assign an output to a function, select the output. A list of possible functions will be shown (including "None"), and the desired function can be selected.
Some outputs will be greyed out if they are hard coded to a particular function.
A list of possible options and what they do is shown below.
Option | Description |
---|---|
LUBE | Powered on when the Pre/Post lube should be active |
START | Powered when the start output is active. For Non-ECU modes, this runs a starter. For an ECU, this may be on the entire run time as a run signal to the ECU, depending on ECU type. |
IDLE | Powered on during idle hold or idle switch selection. The output can then be wired to the idle/rated input of another ECU or speed controller |
PRELUBE PERMISSIVE | Powered on when the prelube permissive is not yet met. Can be used for a lamp |
WARNING LT | Duplicates the warning (yellow) segment of the light tower |
SIREN | Duplicates the siren signal of the light tower |
RED LT | Duplicates the red segment of the light tower |
GREEN LT | Duplicates the green segment of the light tower |
SHUTDOWN ACTIVE | Powered on during the ‘shutdown delay’ state. Can be used for a powered-shut fuel valve |
SUCTION | Suction block valve |
DISCHARGE | Discharge block valve |
BYPASS | Bypass valve |
BLOWDOWN | Blowdown valve |
BATT SAVER | Battery saver active. Should be wired to kill the panel. |
FAULT | Powered when in the faulted state |
WARNING | Powered on when a warning is active |
ADEM DER | Driven Equipment Ready logic to go the ADEM. Powered on when the system is clearing the ECU to start the unit. |
FUEL VALVE | Duplicates the logic of pin 10 of the module. Powered on during normal run to allow for a fuel block valve. |
START GAS SUPPLY | Start gas block valve |
SPEED AUTO | Powered on when the speed is in the auto state |
HOT START | Powered on when the engine is off but not faulted, for hot start |
RESET | Reset broadcast, turns on briefly when reset is pressed |
CYL OIL PUMP | Cylinder oil pump |
SCRB DRAIN | Scrubber drain valve |
COOLER VFD | Cooler VFD run, is generally on when the main motor is on but the start is staggered with a delay |
IGNITION ENBL | Duplicates pin 9 of the annunciator, turns on when the ignition should be enabled |
FLAME DET. FAULT | Powered on when any flame detect alarm is active |