Blowdown With Recycle Sequence

From EMIT Controls
Revision as of 17:34, 21 November 2023 by Thomas Peterson (talk | contribs) (Created page with "==Overview== The Dynamic Control panels have three options related to relieving pressure on a unit: #Blowdown vent, with a simple vent, usually to atmosphere or combuster #Blowdown to header with recycle, where suction and recycle valves are used to relieve to header #Off skid bypass, where an off-skid on/off valve is used to relieve pressure to the header This article covers option (2). ==Setting Up Valves== Before enabling this option, the valve(s) must be configu...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)

Overview

The Dynamic Control panels have three options related to relieving pressure on a unit:

  1. Blowdown vent, with a simple vent, usually to atmosphere or combuster
  2. Blowdown to header with recycle, where suction and recycle valves are used to relieve to header
  3. Off skid bypass, where an off-skid on/off valve is used to relieve pressure to the header

This article covers option (2).

Setting Up Valves

Before enabling this option, the valve(s) must be configured.

  1. The recycle valve can be set up as a normal PID loop named “RECYCLE” that runs off of one input (suction or discharge), or it can use the built-in recycle loop that runs off both suction and discharge. The second option is preferred since it is cleaner. See Dual_Recycle_Setup
  2. The suction valve is set up as a normal PID loop named “SUCTION”

Sequence Setup

The blowdown to header with recycle can be enabled at Settings – Brain – “Outputs Setup” – “Blowdown Settings”. The second tab covers the options for this function, and a screenshot is shown below.

Blowdown recycle.png