- 17:20, 29 July 2022 Thomas Peterson talk contribs created page Default Panel Settings for EDRs (Created page with "When installing an EDR on a panel, find the panel type below and use the settings listed to make sure the EDR can communicate with the panel. ===EMIT EIM=== Under System Settings, navigate to "Modbus". The settings should be: *Communications: 9600,N,8,1 *EIM ID: 10 *Annunciator ID: 70 *EDT ID: 80 ===Altronic DE-3000=== Go to “EDIT SAFETY SHUTDOWNS” -> “MORE MENUS” -> “COMMUNICATIONS”. *NODE should be “1” *PORT 1 is not relevant *PORT 3 should be...")