  • curprev 21:3721:37, 21 July 2022Sean Sanders talk contribs 1,118 bytes +1,118 Created page with "=== CAT->Brain (Annunciator) interface === The CAT panel has one return signal to tell the annunciator that the engine is running. On Panel schematics, this is called “ADEM RUN SIGNAL”, and closes a relay to ground. The contact of the relay is wired to digital input 27, which is automatically filled in as a normal digital input called “ADEM RUN STATUS”. The coil side of the relay is wired to two terminal blocks. On most ADEM systems, the run signal is ground dur..." Tag: Visual edit