EDR Troubleshooting - Incorrect Compressor Data: Revision history

From EMIT Controls

Diff selection: Mark the radio buttons of the revisions to compare and hit enter or the button at the bottom.
Legend: (cur) = difference with latest revision, (prev) = difference with preceding revision, m = minor edit.

    2 July 2024

    • curprev 17:1117:11, 2 July 2024Thomas Peterson talk contribs 3,180 bytes +3,180 Created page with "Symptom: Some data from the compressor is showing up on the site, but some data is missing or incorrect ==Alter port timings== 1. Connect to the wifi terminal. Directions are in Appendix A. 2. In some cases, increasing some port delays can help with communications a. In the wifi terminal under the “Modbus Master” tab, open the heading “Port Timings” b. Increase the Write Delay Us to 50,000 c. Increase the Read delay Us to 4,000 ==Check Base Configuration==..."