Annunciator Purge Setup: Difference between revisions
Sean Sanders (talk | contribs) (Created page with "The annunciator Purge / Blowdown setup screen is used to set up two features: # Low Purge Alarm # High blowdown limit / alarm The setup page is shown below. To reach this page, while in "Engineering" access mode navigate to "Annunciator Setup" -> "Outputs Setup" -> "Purge / Blowdown Limits". Note that neither of these functions will work if autostart or an ECU is not used. <nowiki>*</nowiki>Insert Image* === Annunciator Purge / Blowdown Alarm Setup === ← Controls...") |
|||
(4 intermediate revisions by 2 users not shown) | |||
Line 1: | Line 1: | ||
There are two features related to unit purge: | |||
# Low Purge Alarm | # Low Purge Alarm | ||
# | # Automated purge sequence | ||
Note that either auto-crank or an ECU is needed for these features | |||
=== Low Purge Alarm === | |||
[[File:Purge-limit.png|600px]] | |||
The purge alarm is used to specify a minimum suction level to allow the engine to start. In the above screenshot, this is 10 psi. If the suction is below 10 psi, starting the engine will always go directly to FAULTED. If unused, this can be set to 0. | |||
The | |||
The sensor used for suction does not have to be specified- the system will find the analog input with the name "Suction", "Suction Stg 1", etc. | |||
=== Purge Sequence Setup === | |||
The purge sequence can be used to automatically purge the engine on startup. It requires the presence of a system-controlled suction, bypass, and blowdown valve. The suction valve can be set up as a suction block valve or a proportional suction PID loop. The setup is found at “Settings” -> “Brain” -> “Outputs Setup” -> “Purge Sequence Setup”. The general sequence is: | |||
#Blowdown, bypass, and suction are closed | |||
#Blowdown opened; suction opened (slowly if possible) | |||
#Bypass opened | |||
#Blowdown and suction closed | |||
There are a variety of detailed settings in the sequence, see the setup page for more information. | |||
The purge sequence will not actually be entered unless the “Low Purge Alarm” mentioned above is set to something other than zero. If the suction is below the setting at startup, the purge sequence will run before pre lube. | |||
The | |||
Latest revision as of 22:22, 4 August 2022
There are two features related to unit purge:
- Low Purge Alarm
- Automated purge sequence
Note that either auto-crank or an ECU is needed for these features
Low Purge Alarm
The purge alarm is used to specify a minimum suction level to allow the engine to start. In the above screenshot, this is 10 psi. If the suction is below 10 psi, starting the engine will always go directly to FAULTED. If unused, this can be set to 0.
The sensor used for suction does not have to be specified- the system will find the analog input with the name "Suction", "Suction Stg 1", etc.
Purge Sequence Setup
The purge sequence can be used to automatically purge the engine on startup. It requires the presence of a system-controlled suction, bypass, and blowdown valve. The suction valve can be set up as a suction block valve or a proportional suction PID loop. The setup is found at “Settings” -> “Brain” -> “Outputs Setup” -> “Purge Sequence Setup”. The general sequence is:
- Blowdown, bypass, and suction are closed
- Blowdown opened; suction opened (slowly if possible)
- Bypass opened
- Blowdown and suction closed
There are a variety of detailed settings in the sequence, see the setup page for more information.
The purge sequence will not actually be entered unless the “Low Purge Alarm” mentioned above is set to something other than zero. If the suction is below the setting at startup, the purge sequence will run before pre lube.