Brain battery saver output: Difference between revisions
Falk Alicke (talk | contribs) (Initial draft, just a temporary save) |
Falk Alicke (talk | contribs) m (added a description) |
||
(12 intermediate revisions by 2 users not shown) | |||
Line 1: | Line 1: | ||
==Overview== | ==Overview== | ||
The Battery Saver Function is only available if the panel includes a | The Battery Saver Function is only available if the panel includes a Battery Saver circuit. This feature can also be added to a panel by ordering / installing a 65300-6350 Battery Saver Kit. | ||
The Battery Saver turns off power to the panel when a | The Battery Saver turns off power to the panel when a condition is met, typically the unit not running for a while. All components powered by the panel are powered off when the circuit activates. If an electrical starter or separate engine controller needs also to be powered down, those can be turned off by wiring their power supply through a solenoid switch that is powered by the panel. | ||
The | The Battery Saver can be configured to activate on the following fault conditions: | ||
# Battery Voltage | # Battery Voltage drops below a programmable threshold voltage | ||
# Engine has no RPM for a programmable duration | # Engine has no RPM for a programmable duration | ||
Configuration | ==Configuration== | ||
One digital BRN or BRP output is dedicated to activate the Battery Saver. Example here: DO6. | |||
[[File:Battery Saver Circuit Example.png]] | |||
When DO6 is being activated, the panel will be powered down. Only an on-site operator can reset the system by turning the panel power switch off and back on. To configure DO6 do the following: | |||
(1) Navigate to page 632 or via SETTINGS / BRAIN / OUTPUT SETUP / DIGITAL OUTPUT FUNCTION SELECTION / DO6 and select BATT SAVER | |||
(2) Next navigate to page 674 or via SETTINGS / BRAIN / INPUT SETUP / INPUT VOLTAGE | |||
The most common implementation is to activate the Battery Saver when the engine wasn't running for a certain amount of time. This can be accomplished by using the following configuration. Here the panel will turn off power if RPM was zero for 15 minutes. <span style="color: red;"> ''Notice that the "Duration to be above/below before alarm (seconds)" field was set to 1. This is necessary for the system to accept the 15 minute value. A future software fix will remove the requirement to enter anything but a 0 into this field.'' | |||
[[File:Battery Saver activated by time.png|border|421x421px]] | |||
'''Alternative Configuration:''' | |||
If the Battery Saver should be activated when the battery voltage drops below a certain threshold, DO6 needs to be configured differently. This next example configures DO6 to activate the battery saver if the battery voltage drops below 23.7V for more than 60s. | |||
(1) Navigate to page 658 or via SETTINGS / BRAIN / OUTPUT SETUP / CUSTOM DIGITAL OUT and choose DO6 | |||
(2) Give it a name (e.g. BATT SAVE) | |||
(3) Select INPUT VOLTAGE and set the threshold to 23.7V | |||
(4) Add an on-delay of 60s | |||
[[File:Custom Function Battery Saver.png|border|425x425px]] | |||
'''Testing the System''' | |||
The functionality of the Battery Saver can be verified by powering the panel up and navigating to SETTINGS / BRAIN / OUTPUT STATUS TESTING / DIGITAL OUT TESTING. Here turn the assigned output (e.g. DO6) ON. The panel will turn off and remain off until Power switch SW10 is being depressed and switched ON again. | |||
'''Battery Saver Panel Upgrade Kit:''' | |||
The Battery Saver kit 65300-6350 can be used to update the existing EMIT 14280 panel series with a battery saver implementation. | |||
[[File:BatterySaver Schematic 65300-6450.png|thumb|Battery Saver Aftermarket Solution 65300-6350|left]] |
Latest revision as of 21:06, 29 October 2024
Overview
The Battery Saver Function is only available if the panel includes a Battery Saver circuit. This feature can also be added to a panel by ordering / installing a 65300-6350 Battery Saver Kit.
The Battery Saver turns off power to the panel when a condition is met, typically the unit not running for a while. All components powered by the panel are powered off when the circuit activates. If an electrical starter or separate engine controller needs also to be powered down, those can be turned off by wiring their power supply through a solenoid switch that is powered by the panel.
The Battery Saver can be configured to activate on the following fault conditions:
- Battery Voltage drops below a programmable threshold voltage
- Engine has no RPM for a programmable duration
Configuration
One digital BRN or BRP output is dedicated to activate the Battery Saver. Example here: DO6.
When DO6 is being activated, the panel will be powered down. Only an on-site operator can reset the system by turning the panel power switch off and back on. To configure DO6 do the following:
(1) Navigate to page 632 or via SETTINGS / BRAIN / OUTPUT SETUP / DIGITAL OUTPUT FUNCTION SELECTION / DO6 and select BATT SAVER
(2) Next navigate to page 674 or via SETTINGS / BRAIN / INPUT SETUP / INPUT VOLTAGE
The most common implementation is to activate the Battery Saver when the engine wasn't running for a certain amount of time. This can be accomplished by using the following configuration. Here the panel will turn off power if RPM was zero for 15 minutes. Notice that the "Duration to be above/below before alarm (seconds)" field was set to 1. This is necessary for the system to accept the 15 minute value. A future software fix will remove the requirement to enter anything but a 0 into this field.
Alternative Configuration:
If the Battery Saver should be activated when the battery voltage drops below a certain threshold, DO6 needs to be configured differently. This next example configures DO6 to activate the battery saver if the battery voltage drops below 23.7V for more than 60s.
(1) Navigate to page 658 or via SETTINGS / BRAIN / OUTPUT SETUP / CUSTOM DIGITAL OUT and choose DO6
(2) Give it a name (e.g. BATT SAVE)
(3) Select INPUT VOLTAGE and set the threshold to 23.7V
(4) Add an on-delay of 60s
Testing the System
The functionality of the Battery Saver can be verified by powering the panel up and navigating to SETTINGS / BRAIN / OUTPUT STATUS TESTING / DIGITAL OUT TESTING. Here turn the assigned output (e.g. DO6) ON. The panel will turn off and remain off until Power switch SW10 is being depressed and switched ON again.
Battery Saver Panel Upgrade Kit:
The Battery Saver kit 65300-6350 can be used to update the existing EMIT 14280 panel series with a battery saver implementation.