Some EIMs will not work very well on Modbus because the | Some EIMs will not work very well on Modbus because the EIM responds to messages too quickly. This causes intermittent callout and data issues where there are random missing values. This can be fixed with v2.26 by adjusting the read delay. | ||
=== Updating === | === Updating === |
Latest revision as of 16:39, 13 July 2023
Some EIMs will not work very well on Modbus because the EIM responds to messages too quickly. This causes intermittent callout and data issues where there are random missing values. This can be fixed with v2.26 by adjusting the read delay.
Updating
If the EIM is not at v2.26 or newer (you can check by pressing the "Access" button) it should be updated. See EIM Software Update
The latest file can be found here, download EIM_update_(...).tar: Software Updates
Adjusting the setting
After updating, navigate to "System Settings / Utilities" -> Modbus. The "Setup" password will be needed.
As seen above, a new setting called "Read Delay (ms)" is shown on the right.
Set the read delay to 75 ms, then hit Submit.
The Modbus should now communicate more reliably.