(Created page with "This page shows major changes for software updates, sorted by module. ==DCT== ''' 1.66 - Not yet released ''' #Added standby timer adjustment, req brain 3096, found under Brain Misc Settings #Added some new brain digital output functions #Added TCP/Modbus to VFD connection framework. Currently testing on MV1000 drives. #Add commissioning report under "Information" #Add ECU pct load as a speed control option, requires latest Brain and EDT #Added compressor ratio per al...") |
(→DCT) |
||
Line 43: | Line 43: | ||
#Changed hourmeters to increment based on Brain ‘crank terminate rpm’ rather than fixed RPM, to accommodate low speed units | #Changed hourmeters to increment based on Brain ‘crank terminate rpm’ rather than fixed RPM, to accommodate low speed units | ||
#Fixed ability to activate to ext1 service level | #Fixed ability to activate to ext1 service level | ||
''' 1.60 07-DEC-2022 ''' | |||
#Fixed issue where speed control validation would complain about sensor 2 range incorrectly in some cases | |||
#Add run status Brain output option | |||
#Fix gauge select missing ECU coolant temp | |||
#Added warning dialog if you change a setting and try to go home or back without saving | |||
#Added modbus regs for pid loop status | |||
#Added mass flow rate from EDT support to show on the screen | |||
#Allow for gauge selection of ECU gauges even if there is no ECU | |||
#Added output quick add screen for adding some loops easily | |||
''' 1.58 03-OCT-2022 ''' | |||
#Fixed bug that could cause tc setup to not show asc option when it should | |||
#Change speed control sp to be changeable in operator mode | |||
#Add vibration sensor modbus registers | |||
#Make sure wideband sensor is not an option on new AFRCs that are dual-rich | |||
#Fixed bug where no flow “pct of rated” current value would only work on input 1 | |||
#Added ECU option to turn of thermistors | |||
''' 1.56 11-JUL-2022 ''' | |||
#Fixed a couple ASC issues where some upper rods were still being requested, and three values were incorrectly scaled | |||
#Changed digital valve testing screen to use diagrams for clarity | |||
#Added manifold temp option for sharing from edt to annunciator for some loops | |||
#Added engine de-rate option | |||
#Added option to rename noflow 3 input | |||
''' 1.54 12-MAY-2022 ''' | |||
#Added ESM2 option to EDT. Requires EDT update | |||
#Added VNC option to ethernet setup | |||
#Added logic for rods 5,6 to rod load (including alarm, datalog, and load ctl mode) | |||
#Increased max valve change time to 60 | |||
''' 1.52 03-MAR-2022 ''' | |||
#Added manual mode to recycle pid status. Requires annunciator 2224. | |||
#Added pints per day to the no flow monitoring. | |||
#Added a few items to ECU info – ambient barometric pressure, intake temp, raw manifold voltage. Requires ecu 970. | |||
#Fixed issue where the alarm file read could crash if a line had exactly 9 tokens | |||
#Improvement to the detection of discharge temp indexes | |||
''' 1.50 06-JAN-2022 ''' | |||
#Added ASC to TC input link. Requires brain version 2157. | |||
#Change manual load button to only appear if idle hold is done | |||
#Prevent turning on “Blowdown vent on ESD” if there is no suction block valve | |||
#Added valve testing page | |||
#Added config failsafe to annunciator to fault if config is blank | |||
#Added “Restart load delay on idle” to retention file. It was previously missing. | |||
#Fixed issue where latest CAT SPN was not actually pulled by telematics or datalog | |||
''' 1.48 08-NOV-2021 ''' | |||
#Added EDT setting hints to speed control setup | |||
#Added new CDL items to EDT table and modbus EDT table | |||
#Added modbus option to disallow writes | |||
#Added output option for flame detect status | |||
#Updated load control mode so that if load calc is coming from manifold pressure it will work with GOV/ICM manifold sensor (before only worked with EDT source) | |||
#Added DTC code to ‘Ecu-triggered’ alarms remotely for more info on what went down | |||
#Updated alarm graph screen to show some sensors that can be scrolled through | |||
#Added support for new AEMs that don’t have voltage mode AI/AO | |||
#Added option to have ECU use shutdown pin only instead of CAN | |||
#Added previous uptime to alarms | |||
#Cleaned up valve setup screen to hide AO column normally | |||
#Added manual mode note to valve status gauges if in manual mode | |||
#Added text for input disabled (AI,TI) over previously blank gauges | |||
#Some improvements to datalog graphing to show multiple lines more quickly | |||
#Allow 0s load delay setting |
Revision as of 15:39, 7 June 2024
This page shows major changes for software updates, sorted by module.
DCT
1.66 - Not yet released
- Added standby timer adjustment, req brain 3096, found under Brain Misc Settings
- Added some new brain digital output functions
- Added TCP/Modbus to VFD connection framework. Currently testing on MV1000 drives.
- Add commissioning report under "Information"
- Add ECU pct load as a speed control option, requires latest Brain and EDT
- Added compressor ratio per alarm stage
- Fixed issue with VNC connection where the screen wouldn’t wake during the connection
- Moved pre/post-lube setup to ENG level
- Fixed a few EDT (engine) modbus discrepancies
- Add option to the blowdown on fault to wait for some time first
- Added support for remote updates (requires certain service levels)
- Added main bearing temp deviation shutdown. Requires brain 3110
1.64 25-OCT-2023
- Added ability to change engineering password under system settings
- Fixed issue where operator logs would not download if there was a space in the unit name
- Fixed issue where disabling a expansion module AI would break some random things
- Added auto-change of wifi name to append unit number (if available)
- Added pid5 setpoint reg to modbus
- Added special compressor oil pressure alarm to misc settings (req Brain 2773)
- Removed shutdown cause dialog
- Cleaned up operator log add page to show preview of full log before submitting, instead of several slides of sensor status
- Added cyls 17-20 to EDT values for 3520
- Add settings for ECU stand alone mode
- Add blowdown on normal fault option
- Add versadrive ecu option and pulse output option
- Add ao7/8 modbus regs
- Added auto restart criteria and changed layout of reset logic screen
- Add description to “Touchscreen generated alarm”
- Added icm external timing adjustment, e.g. from detonation module
1.62 07-FEB-2023
- Fix bug where ignition input info screen would not show hall moving on ecu in first box
- Made additional analysis button on alarm screen flash when shown
- Changed hourmeters to increment based on Brain ‘crank terminate rpm’ rather than fixed RPM, to accommodate low speed units
- Fixed ability to activate to ext1 service level
1.60 07-DEC-2022
- Fixed issue where speed control validation would complain about sensor 2 range incorrectly in some cases
- Add run status Brain output option
- Fix gauge select missing ECU coolant temp
- Added warning dialog if you change a setting and try to go home or back without saving
- Added modbus regs for pid loop status
- Added mass flow rate from EDT support to show on the screen
- Allow for gauge selection of ECU gauges even if there is no ECU
- Added output quick add screen for adding some loops easily
1.58 03-OCT-2022
- Fixed bug that could cause tc setup to not show asc option when it should
- Change speed control sp to be changeable in operator mode
- Add vibration sensor modbus registers
- Make sure wideband sensor is not an option on new AFRCs that are dual-rich
- Fixed bug where no flow “pct of rated” current value would only work on input 1
- Added ECU option to turn of thermistors
1.56 11-JUL-2022
- Fixed a couple ASC issues where some upper rods were still being requested, and three values were incorrectly scaled
- Changed digital valve testing screen to use diagrams for clarity
- Added manifold temp option for sharing from edt to annunciator for some loops
- Added engine de-rate option
- Added option to rename noflow 3 input
1.54 12-MAY-2022
- Added ESM2 option to EDT. Requires EDT update
- Added VNC option to ethernet setup
- Added logic for rods 5,6 to rod load (including alarm, datalog, and load ctl mode)
- Increased max valve change time to 60
1.52 03-MAR-2022
- Added manual mode to recycle pid status. Requires annunciator 2224.
- Added pints per day to the no flow monitoring.
- Added a few items to ECU info – ambient barometric pressure, intake temp, raw manifold voltage. Requires ecu 970.
- Fixed issue where the alarm file read could crash if a line had exactly 9 tokens
- Improvement to the detection of discharge temp indexes
1.50 06-JAN-2022
- Added ASC to TC input link. Requires brain version 2157.
- Change manual load button to only appear if idle hold is done
- Prevent turning on “Blowdown vent on ESD” if there is no suction block valve
- Added valve testing page
- Added config failsafe to annunciator to fault if config is blank
- Added “Restart load delay on idle” to retention file. It was previously missing.
- Fixed issue where latest CAT SPN was not actually pulled by telematics or datalog
1.48 08-NOV-2021
- Added EDT setting hints to speed control setup
- Added new CDL items to EDT table and modbus EDT table
- Added modbus option to disallow writes
- Added output option for flame detect status
- Updated load control mode so that if load calc is coming from manifold pressure it will work with GOV/ICM manifold sensor (before only worked with EDT source)
- Added DTC code to ‘Ecu-triggered’ alarms remotely for more info on what went down
- Updated alarm graph screen to show some sensors that can be scrolled through
- Added support for new AEMs that don’t have voltage mode AI/AO
- Added option to have ECU use shutdown pin only instead of CAN
- Added previous uptime to alarms
- Cleaned up valve setup screen to hide AO column normally
- Added manual mode note to valve status gauges if in manual mode
- Added text for input disabled (AI,TI) over previously blank gauges
- Some improvements to datalog graphing to show multiple lines more quickly
- Allow 0s load delay setting