=== ALARMS AND WARNINGS === | === ALARMS AND WARNINGS === | ||
Adjustable alarms and faults are available on the Ignition Alarms screen | Adjustable alarms and faults are available on the Ignition Alarms screen. Alarm thresholds on this screen can be configured at any time to trigger fault conditions for the events listed below. | ||
[[File:Ignition Alarms.jpg]] | [[File:Ignition Alarms.jpg]] | ||
Line 8: | Line 8: | ||
''Ignition Alarms Screen'' | ''Ignition Alarms Screen'' | ||
When an alarm occurs, the “Alarms” button in the | When an alarm occurs, the “Alarms” button in the sidebar of the display will flash the “Alarm” text and display the current number of alarms. To clear the alarm, the “Reset Alarm” button must be selected from the Alarm View screen. The overspeed, underspeed, and critical timing error alarms will shut down the engine. The other diagnostic trigger values will cause an alarm but the engine will stay running. | ||
To set a disable a diagnostic trigger, select the relevant | To set a disable a diagnostic trigger, select the relevant row to Off. Note that “Overspeed RPM” cannot be disabled. | ||
=== RPM | === RPM === | ||
* | * Set the overspeed and underspeed RPM values | ||
* | * The underspeed can be set to 0 to disable | ||
=== Spark Duration === | === Spark Duration === | ||
* A spark duration warning can be configured by defining the | * A spark duration warning can be configured by defining the min and/or max values on this row | ||
* Valid ranges for spark duration are between 0.5 and 20 ms | * Valid ranges for spark duration are between 0.5 and 20 ms | ||
* A spark duration fault provides a warning and does not shutdown the ignition | * A spark duration fault provides a warning and does not shutdown the ignition | ||
Line 35: | Line 28: | ||
* Valid ranges for spark duration deviation are between 0.1 and 10 ms | * Valid ranges for spark duration deviation are between 0.1 and 10 ms | ||
* A spark deviation fault provides a warning and does not shutdown the ignition | * A spark deviation fault provides a warning and does not shutdown the ignition | ||
=== Maximum Cylinder Misfires === | === Maximum Cylinder Misfires === |
Latest revision as of 16:33, 4 August 2022
The ICM presents ignition diagnostics in the form of visual tools, user-defined alarms and warnings, and a quick-view for active faults.
ALARMS AND WARNINGS
Adjustable alarms and faults are available on the Ignition Alarms screen. Alarm thresholds on this screen can be configured at any time to trigger fault conditions for the events listed below.
Ignition Alarms Screen
When an alarm occurs, the “Alarms” button in the sidebar of the display will flash the “Alarm” text and display the current number of alarms. To clear the alarm, the “Reset Alarm” button must be selected from the Alarm View screen. The overspeed, underspeed, and critical timing error alarms will shut down the engine. The other diagnostic trigger values will cause an alarm but the engine will stay running.
To set a disable a diagnostic trigger, select the relevant row to Off. Note that “Overspeed RPM” cannot be disabled.
RPM
- Set the overspeed and underspeed RPM values
- The underspeed can be set to 0 to disable
Spark Duration
- A spark duration warning can be configured by defining the min and/or max values on this row
- Valid ranges for spark duration are between 0.5 and 20 ms
- A spark duration fault provides a warning and does not shutdown the ignition
Spark Deviation from Engine Average
- The spark deviation warning is intended to identify any cylinder or ignition component issues by comparing the individual spark duration with the engine average duration
- Valid ranges for spark duration deviation are between 0.1 and 10 ms
- A spark deviation fault provides a warning and does not shutdown the ignition
Maximum Cylinder Misfires
- If a cylinder’s spark plug is detected to have not sparked properly a misfire count for that cylinder will be incremented
- The Maximum Cylinder Misfires value gives a threshold value past which an alarm will be triggered
- The misfire alarm will show a list of cylinders that are over the threshold value
(Built In) Critical Timing Error – Missing Index
- If the crank TDC index signal has not been detect for 2.0 seconds while the engine is running, the ignition will shutdown and display the fault in the Alarms screen (Pg. 40)
- Potential causes of this fault include:
- TDC magnetic pickup installed too far from the trigger bolt to detect
- Excessive oil and metal shavings on the pole of the TDC magnetic pickup
- Improper wiring of the TDC magnetic pickup
- This error will also show similarly in modes that use a camshaft sensor as a TDC reference if that signal is lost for 2.0 seconds
(Built In) Shutdown Alarms
The Ignition has a variety of shutdown diagnostic alarms that are always enabled. After a shutdown, the EIM will evaluate the conditions of the ignition before and after the engine stopping. If an unusual or problematic condition exists, it will trigger an alarm under code ICM007, and will provide additional information to the user as to what might have contributed to the shutdown.