EDR Troubleshooting - Missing Compressor Data: Difference between revisions

From EMIT Controls
No edit summary
 
Line 35: Line 35:


==Check Configuration==
==Check Configuration==
9. Connect to the EDR wifi console at the location. For instructions, see Appendix A.
9. Connect to the EDR wifi console at the location. For instructions, see Appendix A.
10. Go to the “Alerts” tab of the console
10. Go to the “Alerts” tab of the console
11. Open “Current Run Register”
11. Open “Current Run Register”
12. Verify that the Configuration is correct
12. Verify that the Configuration is correct
a. The ID should be 1, and the Value/Register should be the following depending on annunciator:
a. The ID should be 1, and the Value/Register should be the following depending on annunciator:
i. Murphy Centurion C4: 40191
i. Murphy Centurion C4: 40191
ii. Murphy Centurion Plus: 40641
ii. Murphy Centurion Plus: 40641
iii. Murphy TTD: 40004
iii. Murphy TTD: 40004
iv. Altronic DD40: 40004
iv. Altronic DD40: 40004
v. Altronic DE3000: 40004
v. Altronic DE3000: 40004
vi. EMIT EIM: 31001
vi. EMIT EIM: 31001
vii. Others: See annunciator manual for run status register
vii. Others: See annunciator manual for run status register
b. If the config is not correct, it is possible that the module is not configured at all. See [[EDR_Field_Configuration]] on how to configure an EDR in the field
 
b. If the config is not correct, it is possible that the module is not configured at all. See [[EDR_Field_Configuration]] on how to configure an EDR in the field


==Alter port timings==
==Alter port timings==
13. In some cases, increasing some port delays can help with communications
13. In some cases, increasing some port delays can help with communications
c. In the wifi terminal under the “Modbus Master” tab, open the heading “Port Timings”
c. In the wifi terminal under the “Modbus Master” tab, open the heading “Port Timings”
d. Increase the Write Delay Us to 50,000
d. Increase the Write Delay Us to 50,000
e. Increase the Read delay Us to 4,000
e. Increase the Read delay Us to 4,000


After the above steps there should be some sort of value on the current run register under “Alerts”, and it shouldn’t say TIMEOUT. If it does, there is still an issue, it is possible that either the annunciator or EDR port has a hardware issue.
After the above steps there should be some sort of value on the current run register under “Alerts”, and it shouldn’t say TIMEOUT. If it does, there is still an issue, it is possible that either the annunciator or EDR port has a hardware issue.

Latest revision as of 17:08, 2 July 2024

Symptom: On the Connect site there is no compressor data (e.g. Annunciator Run Code, Suction Pressure, etc.), or on the Wifi console there are expected data items with a timeout of “Never”.

Note that some values may not be present

1. For a TTD or DD40, there won’t be any process pressures or temperatures (though there can be temperatures if a TDXM or DSM are set up). The Run Status and Fault Code should still show up though.

Check EDR Port Setup

2. Under the “Modbus Master” tab of the wifi console, go to the section “Network Configuration”.

3. Typical settings, if not using ethernet:

a. Baud 9600

b. Data size 8 bit

c. Parity none

d. Stop 1

e. “Use Serial” should be checked

f. If anything above is changed, be sure to hit ‘save’ button further down below ‘Use IP’. Note that ‘Use IP’ should not be checked.

Check Panel Modbus Setup

4. The panel should also be set up to 9600 baud. Details on how this is done for different panels is found here: Default_Panel_Settings_for_EDRs

Check Wiring

5. The panel modbus connection should go from pin 4,5 of the EDR to the A,B of the panel. Some panels have multiple modbus ports, see the installation guide for the proper location. EDR Installation Guide 6. The red switch next to pin 5 of the EDR should be on (toward outside of module) 7. Note that for Altronic panels, the wire will connect from “B” of the EDR to “A” of the annunciator, and “B” to “A”. For Murphy or EMIT panels, the wire will connect from “A” to “A” and “B” to “B”. a. Note that wires supplied by EMIT will be labeled with this in mind. 8. Make sure nothing else is wired into the modbus going to the annunciator. Only one SCADA can communicate with an annunciator.

Check Configuration

9. Connect to the EDR wifi console at the location. For instructions, see Appendix A.

10. Go to the “Alerts” tab of the console

11. Open “Current Run Register”

12. Verify that the Configuration is correct

a. The ID should be 1, and the Value/Register should be the following depending on annunciator:

i. Murphy Centurion C4: 40191

ii. Murphy Centurion Plus: 40641

iii. Murphy TTD: 40004

iv. Altronic DD40: 40004

v. Altronic DE3000: 40004

vi. EMIT EIM: 31001

vii. Others: See annunciator manual for run status register

b. If the config is not correct, it is possible that the module is not configured at all. See EDR_Field_Configuration on how to configure an EDR in the field

Alter port timings

13. In some cases, increasing some port delays can help with communications

c. In the wifi terminal under the “Modbus Master” tab, open the heading “Port Timings”

d. Increase the Write Delay Us to 50,000

e. Increase the Read delay Us to 4,000

After the above steps there should be some sort of value on the current run register under “Alerts”, and it shouldn’t say TIMEOUT. If it does, there is still an issue, it is possible that either the annunciator or EDR port has a hardware issue.