Sean Sanders (talk | contribs) (Created page with "The EIM and associated modules are capable of identifying a wide range possible alarm conditions. Depending on the module there are a set of custom and fixed alarms in the system to generate an alarm event for the error condition. See the “ALARMS” section of any of the modules for details on how to configure an alarm. As discussed in the module alarm sections, most alarms can be set up to close the error relay and shutdown the engine on critical alarms (other than an...") |
Sean Sanders (talk | contribs) No edit summary |
||
Line 1: | Line 1: | ||
The | The Governor Alarm Setup page (Pg. 522) specifies alarms for RPM and pressure sensors. An access level of ''Setup'' or higher is needed to see this screen. | ||
<nowiki>*</nowiki>Insert Image* | <nowiki>*</nowiki>Insert Image* | ||
''Governor Alarm Setup'' | |||
The RPM alarm values duplicate the settings from setup step 1. These specify the low and high shutdown values for the engine. If an underspeed is not needed, it can be set to 0. | |||
Each of the three pressure inputs can have an alarm set up for it. To enable an alarm, click the enable “X” on that row, which will allow the parameters for that sensor to be changed. A low alarm, high alarm, and duration can be specified. If the sensor is outside the operating range for longer than the duration, an alarm will be triggered. If the action selected under “Action” is “Warning,” then triggering the alarm only adds the event to the Alarms screen. If the action is “Shutdown,” then the engine will be shut down in addition to adding the event to the alarm screen. | |||
Note | Note: If a “Shutdown” alarm is needed, the alarm relay on the Governor circuit board should be connected to an annunciator panel. During a shutdown the relay is closed to kill the engine. Additionally, the Governor will close the throttle, but this does not guarantee an engine kill. |
Revision as of 17:49, 21 July 2022
The Governor Alarm Setup page (Pg. 522) specifies alarms for RPM and pressure sensors. An access level of Setup or higher is needed to see this screen.
*Insert Image*
Governor Alarm Setup
The RPM alarm values duplicate the settings from setup step 1. These specify the low and high shutdown values for the engine. If an underspeed is not needed, it can be set to 0.
Each of the three pressure inputs can have an alarm set up for it. To enable an alarm, click the enable “X” on that row, which will allow the parameters for that sensor to be changed. A low alarm, high alarm, and duration can be specified. If the sensor is outside the operating range for longer than the duration, an alarm will be triggered. If the action selected under “Action” is “Warning,” then triggering the alarm only adds the event to the Alarms screen. If the action is “Shutdown,” then the engine will be shut down in addition to adding the event to the alarm screen.
Note: If a “Shutdown” alarm is needed, the alarm relay on the Governor circuit board should be connected to an annunciator panel. During a shutdown the relay is closed to kill the engine. Additionally, the Governor will close the throttle, but this does not guarantee an engine kill.