EIM Modbus Temporary Disable: Difference between revisions
Sean Sanders (talk | contribs) (Created page with "Starting with EIM software version 2.00, the modbus can be temporary disabled during a PM to prevent inaccurate callouts during the maintenance. The system will automatically re-enable itself after a time period in case the user does not remember that modbus has been disabled. === Using Modbus Temporary Disable === To use, go to the MODBUS screen under "System Settings". If in "Engineering" password level, the disable button will be shown on the right. <nowiki>*</nowik...") |
Sean Sanders (talk | contribs) m (Sean Sanders moved page Modbus Temporary Disable to EIM Modbus Temporary Disable) |
(No difference)
|
Revision as of 17:59, 26 July 2022
Starting with EIM software version 2.00, the modbus can be temporary disabled during a PM to prevent inaccurate callouts during the maintenance. The system will automatically re-enable itself after a time period in case the user does not remember that modbus has been disabled.
Using Modbus Temporary Disable
To use, go to the MODBUS screen under "System Settings". If in "Engineering" password level, the disable button will be shown on the right.
*Insert Image*
After clicking 'Disable...' a confirmation dialog will come up. If 'Yes' is selected to disable, the number of hours will be asked.
*Insert Image*
The system will not respond to any modbus requests (either over serial 485 or TCP/Ethernet) until the timer expires, or the user manually re-enables the port, whichever comes first.
*Insert Image*
If the port is disabled, and the 'Disabled' button is selected, a dialog will ask the user if Modbus should be re-enabled immediately. Otherwise the timer will run out normally and re-enable automatically. The enable time is saved to disk, so the system can be power cycled multiple times and it will not affect the enabling.
Note: If the clock is changed during the disable period, it may clear the disable timer.