Annunciator Output Testing
From EMIT Controls
Revision as of 21:58, 5 August 2022 by Thomas Peterson (talk | contribs) (Thomas Peterson moved page Annunciator Digital Out Test Screen to Annunciator Output Testing without leaving a redirect)
Overview
The digital out test screen is used to test the digital outputs (especially during install).
The screen is reached from the home page by selecting Settings -> Brain -> "Output Status / Testing" -> "Digital Out Testing"
To use this page, the system must be in a stopped state. Select "Force ON" or "Force OFF" to force an output to that level for testing.
Select "Clear Test / Done" to remove all forced commands and return the outputs to their normal state. (Note: Some outputs will still be normally on when the unit is stopped, such as hot start).
If "RESET" or "STOP" is ever pressed on the panel, all forced output states will be cleared immediately.