20240 EMD Modbus Table
From EMIT Controls
Revision as of 18:13, 15 December 2023 by Thomas Peterson (talk | contribs) (Created page with "{| class="wikitable" |+ |- ! Register !! Description !! Pin(s) !! Offset !! Scale |- | 30001 || Thermocouple 1 Reading || 24-25 || -273 || 0.03125 |- | 30002 || Thermocouple 2 Reading || 26-27 || -273 || 0.03125 |- | 30003 || Thermocouple 3 Reading || 28-29 || -273 || 0.03125 |- | 30004 || Thermocouple 4 Reading || 30-31 || -273 || 0.03125 |- | 30005 || Thermocouple 5 Reading || 32-33 || -273 || 0.03125 |- | 30006 || Thermocouple 6 Reading || 34-35 || -273 || 0.03125 |...")
Register | Description | Pin(s) | Offset | Scale |
---|---|---|---|---|
30001 | Thermocouple 1 Reading | 24-25 | -273 | 0.03125 |
30002 | Thermocouple 2 Reading | 26-27 | -273 | 0.03125 |
30003 | Thermocouple 3 Reading | 28-29 | -273 | 0.03125 |
30004 | Thermocouple 4 Reading | 30-31 | -273 | 0.03125 |
30005 | Thermocouple 5 Reading | 32-33 | -273 | 0.03125 |
30006 | Thermocouple 6 Reading | 34-35 | -273 | 0.03125 |
30007 | Thermistor 1 Reading* | 36 | -273 | 0.03125 |
30008 | Thermistor 2 Reading* | 38 | -273 | 0.03125 |
30103 | Analog Input 1 Voltage (V) | 20 | 0 | 0.0001 |
30104 | Analog Input 1 Current (mA) | 20 | 0 | 0.01 |
30105 | Analog Input 2 Voltage (V) | 23 | 0 | 0.0001 |
30106 | Analog Input 2 Current (mA) | 23 | 0 | 0.01 |
30107 | Analog Input 3 Voltage (V) | 45 | 0 | 0.0001 |
30108 | Analog Input 3 Current (mA) | 45 | 0 | 0.01 |
30109 | Analog Input 4 Voltage (V) | 42 | 0 | 0.0001 |
30110 | Analog Input 4 Current (mA) | 42 | 0 | 0.01 |
30111 | Analog Input 5 Voltage (V) | 19 | 0 | 0.0001 |
30112 | Analog Input 5 Current (mA) | 19 | 0 | 0.01 |
30114 | Analog Input 6 Current (mA)* | 36 | 0 | 0.01 |
30115 | Analog Input 7 Current (mA)* | 38 | 0 | 0.01 |
30211 | Digital Input 1 (1 = closed to ground) | 39 | 0 | 1 |
30212 | Digital Input 2 | 41 | 0 | 1 |