20240 EMD Modbus Table

From EMIT Controls
Revision as of 18:13, 15 December 2023 by Thomas Peterson (talk | contribs) (Created page with "{| class="wikitable" |+ |- ! Register !! Description !! Pin(s) !! Offset !! Scale |- | 30001 || Thermocouple 1 Reading || 24-25 || -273 || 0.03125 |- | 30002 || Thermocouple 2 Reading || 26-27 || -273 || 0.03125 |- | 30003 || Thermocouple 3 Reading || 28-29 || -273 || 0.03125 |- | 30004 || Thermocouple 4 Reading || 30-31 || -273 || 0.03125 |- | 30005 || Thermocouple 5 Reading || 32-33 || -273 || 0.03125 |- | 30006 || Thermocouple 6 Reading || 34-35 || -273 || 0.03125 |...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Register Description Pin(s) Offset Scale
30001 Thermocouple 1 Reading 24-25 -273 0.03125
30002 Thermocouple 2 Reading 26-27 -273 0.03125
30003 Thermocouple 3 Reading 28-29 -273 0.03125
30004 Thermocouple 4 Reading 30-31 -273 0.03125
30005 Thermocouple 5 Reading 32-33 -273 0.03125
30006 Thermocouple 6 Reading 34-35 -273 0.03125
30007 Thermistor 1 Reading* 36 -273 0.03125
30008 Thermistor 2 Reading* 38 -273 0.03125
30103 Analog Input 1 Voltage (V) 20 0 0.0001
30104 Analog Input 1 Current (mA) 20 0 0.01
30105 Analog Input 2 Voltage (V) 23 0 0.0001
30106 Analog Input 2 Current (mA) 23 0 0.01
30107 Analog Input 3 Voltage (V) 45 0 0.0001
30108 Analog Input 3 Current (mA) 45 0 0.01
30109 Analog Input 4 Voltage (V) 42 0 0.0001
30110 Analog Input 4 Current (mA) 42 0 0.01
30111 Analog Input 5 Voltage (V) 19 0 0.0001
30112 Analog Input 5 Current (mA) 19 0 0.01
30114 Analog Input 6 Current (mA)* 36 0 0.01
30115 Analog Input 7 Current (mA)* 38 0 0.01
30211 Digital Input 1 (1 = closed to ground) 39 0 1
30212 Digital Input 2 41 0 1