Adding Engine Failure Status: Revision history

From EMIT Controls

Diff selection: Mark the radio buttons of the revisions to compare and hit enter or the button at the bottom.
Legend: (cur) = difference with latest revision, (prev) = difference with preceding revision, m = minor edit.

    5 August 2022

    • curprev 17:2317:23, 5 August 2022Thomas Peterson talk contribs 1,489 bytes +1,489 Created page with "==Overview== Currently, most panels use the “Engine running” signal from the CAT(r) panel to determine if the engine is running. It goes to DI-27 as a B1 or B2 digital input, and is used for some minor other logic. CAT(r) has another signal, “Engine failure” that can be added to another digital input as an ‘A’ shutdown. This will prevent the annunciator from entering the start sequence if the CAT(r) panel is faulted (even though the engine would not start i..."