Adding Temps from TDXM: Revision history

From EMIT Controls

Diff selection: Mark the radio buttons of the revisions to compare and hit enter or the button at the bottom.
Legend: (cur) = difference with latest revision, (prev) = difference with preceding revision, m = minor edit.

    30 August 2022

    • curprev 22:2522:25, 30 August 2022Thomas Peterson talk contribs 583 bytes +583 Created page with "Normally an EDR connected to a TTD only gets the run code, rpm, and battery voltage. Optionally, the TDXM can be connected as well to get the temperatures. Steps: # On the TDXM go to the setup menu setpoint 7, and set "RTU" to "2" and "baud" to "0" # With two wires, connect the "A" of the TTD to the "A" of the TDXM, and "B" to "B" # Connect to the EDR WiFi Console, see EDR Wi-Fi Console # Open the modbus master page, then the modbus master table # For each row that..."