Adding Temps from TDXM
From EMIT Controls
Normally an EDR connected to a TTD only gets the run code, rpm, and battery voltage. Optionally, the TDXM can be connected as well to get the temperatures.
Steps:
- On the TDXM go to the setup menu setpoint 7, and set "RTU" to "2" and "baud" to "0"
- With two wires, connect the "A" of the TTD to the "A" of the TDXM, and "B" to "B"
- Connect to the EDR WiFi Console, see EDR Wi-Fi Console
- Open the modbus master page, then the modbus master table
- For each row that contains a valid temperature, change the ID column to "2" and the register column to 40000+[channel number]