Adding Temps from TDXM
From EMIT Controls
Revision as of 22:25, 30 August 2022 by Thomas Peterson (talk | contribs) (Created page with "Normally an EDR connected to a TTD only gets the run code, rpm, and battery voltage. Optionally, the TDXM can be connected as well to get the temperatures. Steps: # On the TDXM go to the setup menu setpoint 7, and set "RTU" to "2" and "baud" to "0" # With two wires, connect the "A" of the TTD to the "A" of the TDXM, and "B" to "B" # Connect to the EDR WiFi Console, see EDR Wi-Fi Console # Open the modbus master page, then the modbus master table # For each row that...")
Normally an EDR connected to a TTD only gets the run code, rpm, and battery voltage. Optionally, the TDXM can be connected as well to get the temperatures.
Steps:
- On the TDXM go to the setup menu setpoint 7, and set "RTU" to "2" and "baud" to "0"
- With two wires, connect the "A" of the TTD to the "A" of the TDXM, and "B" to "B"
- Connect to the EDR WiFi Console, see EDR Wi-Fi Console
- Open the modbus master page, then the modbus master table
- For each row that contains a valid temperature, change the ID column to "2" and the register column to 40000+[channel number]