Annunciator Setup - Class B & C Timers

From EMIT Controls

The B/C timer setup page can be found at Settings - Brain - Timers Setup - Class B/C Timer Lengths. This page is used to adjust B/C timer settings.

B-C-page.PNG

Both B timers will count down from any RESET button press or once the unit is started, and when they reach zero will arm the inputs of that class. Generally the B2 timer should be the shorter timer, intended for items that should clear during the very initial startup of the engine such as oil pressure.

The maximum C time can be optionally set on this page, or set to 0 if not used. If used, this timer will count down from the RESET button press, and when it expires will globally arm all C inputs, even if they have not cleared yet. This prevents a C contact from never arming before the operator leaves the site.