Light Tower and Siren Logic
From EMIT Controls
Overview
The standard EMIT panel comes with a three color light tower (red, green, yellow) and siren/buzzer. There is hard-coded logic that drives the color and siren state.
Siren Logic
The siren will sound in these scenarios:
- If crank control used, during start of crank for user-defined period the siren will sound
- When a remote or auto reset of the unit is triggered the siren will sound for 6 seconds
- Before blowing down the siren will sound for 4 seconds in pair of two short beeps per second
- If a custom siren sensor condition is set up, the siren will sound when the sensor condition is present (See Annunciator Setup - Buzzer)
Light Tower Logic
Normal Running
- If the panel state is not running (stopped, standby, faulted, pending restart, or transitioning to stop) the tower will show red
- If the panel is in a running state and there is no warning active, the tower will show green
- If the panel is in a running state and there is a warning active, the tower will show yellow
Special scenarios
- During test mode the tower will blink yellow with one long blink when an input faults and two short blinks when an input unfaults
- If crank control is used, the tower will blink green/yellow while cranking
- If an auto restart is pending the tower will blink yellow/red continuously
- 5 seconds before the B1 timer expires the tower will blink green/yellow to warn about the timer about to expire
- When running cooldown mode the tower will show yellow continuously